Application
| Caliber
(mm) |
20 | 25 | 32 | 50 | 80 | 100 | 150 | 200 |
| Flow Range
(m3/h) |
1.2~15 | 2.5~30 | 4.5~60 | 10~150 | 28~400 | 50~800 | 150~2250 | 360~3600 |
| Accuracy | 1.0~1.5% | |||||||
| Repeatability | Less than 1/3 of basic error absolute value | |||||||
| Working Pressure
(MPa) |
1.6Mpa, 2.5Mpa, 4.0Mpa, 6.3Mpa
Special pressure please double check |
|||||||
| Application Condition | Environment temperature: -30℃~+65℃
Relative humidity: 5%~95% Medium temperature: -20℃~+80℃ Atmospheric pressure: 86KPa~106KPa |
|||||||
| Working Power | 24VDC+3.6V battery power, can remove the battery | |||||||
| Output Signal | 4-20mA, pulse, RS485, alarm | |||||||
| Applicable Medium | All gases (except steam) | |||||||
| Explosion-proof Mark | Ex ia II C T6 Ga | |||||||

| Caliber
(mm) |
Length
(mm) |
PN1.6~4.0MPa | |||||||||||||||||
| H | Dφ | Kφ | N | L | dφ | H | Dφ | Kφ | N | L | dφ | H | Dφ | Kφ | N | L | dφ | ||
| 25 | 200 | 305 | 115 | 85 | 4 | 14 | 65 | ||||||||||||
| 32 | 200 | 320 | 140 | 100 | 4 | 18 | 76 | ||||||||||||
| 50 | 230 | 330 | 165 | 125 | 4 | 18 | 99 | ||||||||||||
| 80 | 330 | 360 | 200 | 160 | 8 | 18 | 132 | ||||||||||||
| PN1.6MPa | ※PN2.5~4.0MPa | ||||||||||||||||||
| 100 | 410 | 376 | 220 | 180 | 8 | 18 | 156 | 390 | 235 | 190 | 8 | 22 | 156 | ||||||
| 150 | 570 | 430 | 285 | 240 | 8 | 22 | 211 | 450 | 300 | 250 | 8 | 26 | 211 | ||||||
| PN1.6MPa | PN2.5MPa | ※PN4.0MPa | |||||||||||||||||
| 200 | 700 | 470 | 340 | 295 | 12 | 22 | 266 | 490 | 360 | 310 | 12 | 26 | 274 | 510 | 375 | 320 | 12 | 30 | 284 |
| DN(mm) | Type | Flow Range (m³/h) |
Working Pressure (MPa) | Accuracy Level | Repeatability |
| 20 | 1.2~15 | 1.6
2.5 4.0 6.3 |
1.0
1.5 |
Less than 1/3 of basic error absolute value | |
| 25 | 2.5~30 | ||||
| 32 | 4.5~60 | ||||
| 50 | B | 10~150 | |||
| 80 | B | 28~400 | |||
| 100 | B | 50~800 | |||
| 150 | B | 150~2250 | |||
| 200 | 360~3600 |
| LUGB | XXX | X | X | X | X | X | X | X | X | X | |
| Caliber (mm) |
DN25-DN200 Reference Code, please check caliber code table 1 |
||||||||||
| Function | With temperature & pressure compensation | Y | |||||||||
| Without temperature & pressure compensation | N | ||||||||||
| Nominal Pressure |
1.6Mpa | 1 | |||||||||
| 2.5Mpa | 2 | ||||||||||
| 4.0Mpa | 3 | ||||||||||
| 6.3Mpa | 4 | ||||||||||
| Others | 5 | ||||||||||
| Connection | Flange | 1 | |||||||||
| Thread | 2 | ||||||||||
| WAFER | 3 | ||||||||||
| Others | 4 | ||||||||||
| Output Signal | 4-20mA,pulse (two-wire system) | 1 | |||||||||
| 4-20mA,pulse (three-wire system) | 2 | ||||||||||
| RS485 communication | 3 | ||||||||||
| 4-20mA, pulse,HART | 4 | ||||||||||
| Others | 5 | ||||||||||
| Alarm | Low and high limit Alarm | 6 | |||||||||
| Without | 7 | ||||||||||
| Accuracy Level | 1.0 | 1 | |||||||||
| 1.5 | 2 | ||||||||||
| Cable Entry | M20X1.5 | M | |||||||||
| 1/2” NPT | N | ||||||||||
| Structure Type |
Compact/Integral | 1 | |||||||||
| Remote | 2 | ||||||||||
| Power Supply |
3.6V Lithium Battery,DC24V | A | |||||||||
| DC24V | D | ||||||||||
| 3.6V Lithium Battery | E | ||||||||||
| Ex-proof | With Ex-proof | 0 | |||||||||
| Without Ex-proof | 1 | ||||||||||
| Shell Material | Stainless Steel | S | |||||||||
| Aluminium Alloy | L | ||||||||||
| Process Connection |
DIN PN16 | 1 | |||||||||
| DIN PN25 | 2 | ||||||||||
| DIN PN40 | 3 | ||||||||||
| ANSI 150# | 4 | ||||||||||
| ANSI 300# | A | ||||||||||
| ANSI 600# | B | ||||||||||
| JIS 10K | C | ||||||||||
| JIS 20K | D | ||||||||||
| JIS 40K | E | ||||||||||
| Others | F | ||||||||||
Installation
.jpg)
2. Precession vortex flow meter maintenance
(1) On-site installation and maintenance must comply with the warning “Do not open the cover when there is explosive gas”, and turn off the external power supply before opening the cover.
(2) When the pipeline is installed and tested for tightness, pay attention to the very high pressure that the pressure sensor of the vortex flowmeter can withstand, so as not to damage the pressure sensor.
(3) When it is put into operation, the upstream and downstream valves of the flow meter should be opened slowly to avoid the instantaneous air flow damaging the meter and pipeline.
(4) When the flowmeter needs to have remote signal transmission, it should be connected to the external power supply 24VDC strictly according to the requirements of 3 and 4 “Electrical Performance Index”, and it is strictly forbidden to directly connect the 220VAC or 380VAC power supply to the signal input port.
(5) The user is not allowed to change the wiring method of the explosion-proof system and arbitrarily twist each output lead connector;
(6) When the flowmeter is running, it is not allowed to open the front cover to change the instrument parameters, otherwise it will affect the normal operation of the precession vortex flowmeter
(7) Do not loosen the fixed part of the flowmeter at will.
(8) When the product is used outdoors, it is recommended to add a waterproof cover.