Application
| Explosion-proof Grade | Exia IIC T6 Ga |
| Measuring Range | 30 meters |
| Frequency | 26 GHz |
| Temperature: | -60℃~ 150℃ |
| Measurement Precision | ±2mm |
| Process Pressure | -0.1~4.0 MPa |
| The Signal Output | (4~20)mA/HART(Two wire/Four)RS485/Modbus |
| The Scene Display | Four digital LCD |
| Shell | Aluminum |
| Connection | Flange (optional)/Thread |
| Protection Grade | IP67 |

| RD92 | X | X | X | X | X | X | X | X | |
| License | Standard (Non-explosion-proof) | P | |||||||
| Intrinsically safe (Exia IIC T6 Ga) | I | ||||||||
| Intrinsically safe type, Flameproof (Exd (ia) IIC T6 Ga) | G | ||||||||
| Process Connection / Material | Thread G1½″A / Stainless Steel 304 | G | |||||||
| Thread 1½″ NPT / Stainless Steel 304 | N | ||||||||
| Flange DN50 / Stainless Steel 304 | A | ||||||||
| Flange DN80 / Stainless Steel 304 | B | ||||||||
| Flange DN100 / Stainless Steel 304 | C | ||||||||
| Special Custom-tailor | Y | ||||||||
| Antenna Type / Material | Horn Antenna Φ46mm / Stainless Steel 304 | A | |||||||
| Horn Antenna Φ76mm / Stainless Steel 304 | B | ||||||||
| Horn Antenna Φ96mm / Stainless Steel 304 | C | ||||||||
| Special Custom-tailor | Y | ||||||||
| Seal Up / Process Temperature | Viton / (-40~150) ℃ | V | |||||||
| Kalrez / (-40~250) ℃ | K | ||||||||
| The Electronic Unit | (4~20) mA / 24V DC / Two wire system | 2 | |||||||
| (4~20) mA / 24V DC / HART two wire system | 3 | ||||||||
| (4~20) mA / 220V AC / Four wire system | 4 | ||||||||
| RS485 / Modbus | 5 | ||||||||
| Shell / Protection Grade | Aluminum / IP67 | L | |||||||
| Stainless Steel 304L/ IP67 | G | ||||||||
| Cable Line | M 20×1.5 | M | |||||||
| ½″ NPT | N | ||||||||
| Field Display/The Programmer | With | A | |||||||
| Without | X | ||||||||
Installation
Radar Level Meter Maintenance
1. Confirm whether the grounding protection is in place. To prevent electrical leakage from causing damage to electrical components and interference with normal signal transmission, remember to ground either end of the radar meter and the signal interface of the control room cabinet.
2. Whether lightning protection measures are in place. Although the radar level gauge itself supports this function, external lightning protection measures must be taken.
3. The field junction box must be installed strictly in accordance with the installation instructions, and waterproof measures must be taken.
4. The field wiring terminals must be sealed and isolated to prevent liquid intrusion from causing short circuits in the power supply, wiring terminals and circuit board corrosion.
Submit your specifications for a comprehensive quotation and feasibility study.